Suntree DC Load Disconnect
The elasticaccumulating accelerating mechanism for instant release realize the rapid making and breaking (13.8m/s), having no relationship with the speed of the operating handle, and increasing greatly the capability ofextinguishing electric arc.
• The sheu made of unsaturated polyester resin reinforced by glass fiber possesses excellent performance of flame resistant, dialectic performance, safe operation, resist carbonic performance and resist impact performance.
• Parallel double gap contact possesses self cleaning functions.
• All the contact materials are copper alloy plated with silver, and possess two separation contact surfaces.
• Large clearance of insulation.
• Be on “0”, the products can lock the handle with three locks at the same time and thus can avoid error operation.
In stock
FREE URBAN SHIPPING on all batteries.
For delivery outside of main centres, please contact us for a quote.
Suntree DC Load Disconnect
The elasticaccumulating accelerating mechanism for instant release realize the rapid making and breaking (13.8m/s), having no relationship with the speed of the operating handle, and increasing greatly the capability ofextinguishing electric arc.
• The sheu made of unsaturated polyester resin reinforced by glass fiber possesses excellent performance of flame resistant, dialectic performance, safe operation, resist carbonic performance and resist impact performance.
• Parallel double gap contact possesses self cleaning functions.
• All the contact materials are copper alloy plated with silver, and possess two separation contact surfaces.
• Large clearance of insulation.
• Be on "0", the products can lock the handle with three locks at the same time and thus can avoid error operation.
rated voltage V | DC 1000V / DC 1500V |
Number of pole | 2P |
utilization category | see table below |
Frame Current | 320A |
Rated Insulation voltageV | 1600V |
rated operational voltage A | 32A-500A |
Rated impulse withstand voltage kA | 12 |
short-time withstand current kA | 8/1s |
short-circuit making capacity kA | 15 |
technical life | 10000 |
Electrical Lifetime | 1000 |
Maximum conductor section mm² | 150(2pcs) |
tightening torque Nm | 10 |
Installation method | Screw installation, cabinet door installation |
Meet xxxx | IEC 60947-3 GB/T14048.3 |
International Protection | IP20 |
Service temperature | -40~+70℃ |
storage temperature | -50~+70℃ |
altitude | ≤2000m |
pollution-level | 3 |
Certification | CCC 、TUV、CB、CE、ROHS |