SK12V314PH and Victron Communication

Out of the box, Victron hardware will not communicate with the Cerbo or GX devices as the CAN bus’s default speed does not match what the Sk12V314 requires.
Configuring the SK12V314PH to communicate with the Cerbo is the same as configuring the SK48V100.
If the battery is not detected by the Cerbo:
• Ensure the cable is plugged in properly, and that a CANBUS terminator is
inserted in the unused port
• Enter main menu and select “Settings”. Scroll down to the “Services” selection.
• Under BMS-CAN port, ensure CAN-bus BMS is set to 500 kbit/s.